FA-AVR-150V-30KVA/SVR3PH

Benefits

  • High Efficiency
  • 100% Unbalanced loadind capability between three phasees
  • Digital Display
  • Advanced protection
  • Strong Overload ability
  • Configurable Normal Output Voltage (optional)
  • Isolated manual Bypass switch
  • Surge protection Device (optional)
  • Servo Motor type

Features

FA-AVR-150V-10KVASVR1PH FEATURES
30KVA

Specification

Model number FA-AVR-150V-30KVA/SVR3PH
INPUT
Rated Input Voltage L1—L2/380V L2—L3/380V L1—L3/380V
Input Voltage Range 260-430V or customized
Input frequency 45-65HZ
Power Factor 0.98
OUTPUT
Rated Output Voltage L1—L2/380V L2—L3/380V L1—L3/380V
Output Precision ±3% (±1% optional)
Response time <1s, against 10% variation of input voltage
Efficiency >96%
Loading Ability 120% for 180s, 150% for 30s, 200% for 10s, 300% for 5s
DISPLAY
Input Voltage Line Voltage AB,BC, CA     Phase Voltage A, B, C
Output Voltage Line Voltage AB,BC, CA     Phase Voltage A, B, C
Output Current Phase Current: A, B, C
PROTECTION AND ALARM
Output Under Voltage Output cuttoff by contactor + “L” in display + Buzzer beeping
Output Over Voltage Output cuttoff by contactor + “H” in display + Buzzer beeping
Overload Output cuttoff by contactor + “F” in display + Buzzer beeping
Over Termperature Output cuttoff by contactor + “C” in display + Buzzer beeping
Phase failure Output cuttoff by contactor + Buzzer beeping
Wrong Phase sequency Cant switch on regulator “P” in display + Buszzer beeping
Short Circuit Input cutoff by air breaker
Bypass Isolated manual bypass switch
Output Delay time 6s/180s selectable
Surge/Spike Optional, Replaceable SPD
SAFETY
Insulation V / R 2,000V/60s / >5MΩ
Creepage Distance >8mm
Grounding Resistance >0.1MΩ
Insulation Class of coil Class F (155C)
Cooling Mode Cooling Fan
IP Level IP20
Audible Noice <65dB at 1m distance with full load
OPERATING CONDITIONS
operating Termperture – 5°C – + 45°C
Operating  humidity 10%-90%, non-condesing