MODEL |
FA-UPSX-240V-30KVA-1PH |
FA-UPSX-240V-50KVA-1PH |
PHASE |
1-phase in/1-phase out |
Cabinet Capacity |
30KW |
50KW |
BATTERY TYPE |
Built-in Battery or External Battery |
ONE POWER MODULE CAPACITY |
6KVA / 6KW or 10KVA / 10KW |
MAX. POWER MODULE NO. |
5 |
INPUT |
Nominal Voltage |
220/230Vac |
Voltage Range |
120~276Vac |
Nominal Frequency |
50/60Hz (Auto Sensing) |
Frequency Range |
40Hz ~70Hz |
Power Factor |
> 0.99 @ 100% Load , >0.98 @ 50% Load |
Harmonic Distortion (THDi) |
< 3% @ 100% load |
OUTPUT |
Nominal Voltage |
220/230Vac |
Voltage Regulation (Steady state) |
< ± 1% Typical (balanced load) ; <± 2% Typical (unbalanced load) |
Nominal Frequency |
50/60Hz |
Frequency Range (Synchronized) |
46Hz ~ 54Hz or 56Hz ~ 64Hz |
Overload Capability |
1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150% |
Harmonic Distortion |
<2% THD (Linear Load) ; <4% THD (Non-linear Load) |
Efficiency |
Up to 94.5% |
BATTERY / CHARGER |
Numbers |
16~20 pcs (Adjustable) |
Charging Voltage |
+/- 13.7V x N (N=16~20) |
Temperature Compensation |
Yes |
Maximum Charging Current Per Module) |
6A |
PHYSICAL |
Cabinet Dimension (D x W x H) mm |
840×600×1400 |
840×600×2000 |
Net Weight (Kg) |
138 |
150 |
ENVIRONMENT |
Operating Temperature |
0 ~ 40°C |
Relative Humidity |
0 ~ 95% non-condensing |
MANAGEMENT |
Optional SNMP |
Power management from SNMP manager and web browser |