Model |
FA-UPSX-±240v-60KVA-3PH |
FA-UPSX-±240v-90KVA-3PH |
FA-UPSX-±240v-120KVA-3PH |
FA-UPSX-±240v-80KVA/120KVA-3PH |
FA-UPSX-±240v-120KVA/180KVA-3PH |
FA-UPSX-±240v-200KVA-3PH |
FA-UPSX-±240v-210KVA-3PH |
FA-UPSX-±240v-300KVA-3PH |
PHASE |
3-phase in/3-phase out |
CABINET CAPACITY* |
60KW |
90 KW |
120 KW |
120 KW or |
180 KW or |
200 KW |
210 KW |
300 KW |
80 KW |
120 KW |
BATTERY TYPE |
Built-in Battery or External Battery |
ONE POWER MODULE CAPACITY |
20KVA / 20KW |
30KVA / 30KW |
30KVA / 30KW or 20KVA / 20KW |
20KVA / 20KW |
30KVA / 30KW |
MAX. POWER MODULE NO. |
3 |
3 |
4 |
4 |
6 |
10 |
8 |
10 |
MAX. BATTERY SET NO.** |
3 |
3 |
5 |
– |
– |
– |
– |
– |
INPUT |
Nominal Voltage |
3 x 380VAC/400VAC/415VAC (3Ph+N) |
Voltage Range |
305 ~ 478 VAC at 100% load; 208 ~ 304VAC at <70% load |
Nominal Frequency |
50/60Hz (Auto Sensing) |
Frequency Range |
40Hz ~70Hz |
Power Factor |
> 0.99 @ 100% Load , >0.98 @ 50% Load |
Harmonic Distortion (THDi) |
< 3% @ 100% load |
OUTPUT |
Nominal Voltage |
3 x 380VAC/400VAC/415VAC (3Ph+N) |
Voltage Regulation (Steady state) |
≦ ± 1% Typical (balanced load) ; ≦ ± 2% Typical (unbalanced load) |
Nominal Frequency |
50/60Hz |
Frequency Range (Synchronized) |
46Hz ~ 54Hz or 56Hz ~ 64Hz |
Overload Capability |
1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150% |
Harmonic Distortion |
≦2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) |
Efficiency |
Up to 94.5% |
BATTERY / CHARGER |
Numbers |
32~40 pcs (Adjustable) |
Charging Voltage |
+/- 13.7V x N (N=32~40) |
Maximum Charging Current |
8A for 30KW |
Per Module) |
6A for 20KW |
PHYSICAL |
Cabinet Dimension (D x W x H) mm |
840×600×1400 |
1100 x 600 x 1475 |
1100 x 600 x 2010 |
1100 x 600 x 1475 |
1100 x 600 x 1475 |
1100 x 600 x 2010 |
Net Weight (Kg) |
149 |
675 |
932 |
335 |
437.5 |
611 |
549 |
620 |
ENVIRONMENT |
Operating Temperature |
|
0 ~ 40°C |
Relative Humidity |
|
0 ~ 95% non-condensing |
MANAGEMENT |
Optional SNMP |
|
Power management from SNMP manager and web browser |