MODEL NUMBER |
FA-INV-12V-750VA |
FA-INV-12V-850VA |
FA-INV-12V-1100VA |
FA-INV-12V-1500VA |
Capacity |
750VA/490W |
850VA/620W |
1100VA/730W |
1500VA/1000W |
NARROW MODE |
Mains undervoltage cutoff /recovery |
180 V / 190 V |
Mains overvoltage cutoff /recovery |
265 V / 255 V |
Battery charging voltage |
180 VAC to 265 VAC |
Changeover time |
≤ 10 milliseconds |
Output voltage (no load) |
230 V |
WIDE MODE |
Mains undervoltage cutoff /recovery |
100 V / 110 V |
Mains overvoltage cutoff /recovery |
295 V / 285 V |
Battery charging voltage |
100 VAC to 295 VAC |
Changeover time |
≤ 20 milliseconds |
Output voltage (no load) |
230 V |
BATTERY |
Quick charge current |
14A |
Normal charge current |
10A |
Boost charge voltage |
14.5V |
Float charge voltage |
13.8V |
Low battery cutoff point |
10.4V |
Number of batteries |
1 *12VDC |
Recommended battery |
65 AH to 200 AH |
Charge method |
Constant current ,followed by constant voltage |
Output waveform |
Pure sine wave |
Output frequency (UPS mode) |
50 HZ |
Efficiency |
≥80% |
Operation temperature |
0 to 45°C |
LED indicators |
Mains,charging,UPS,low battery, overload |
Audible alarm |
Low battery,overload,short circuit |
PROTECTIONS |
Overload |
105% load on UPS (auto reset within 5 re-tries) |
overcharge |
Control battery voltage and current through software |
Short circuit |
MCB Tripe in Main mode and UPS gets shut down in Back-up mode |
Thermal |
UPS get shut down when temperature reaches to 95 C at inside UPS |
Battery reverse polarity |
DC fuse on PMB will fail when battery terminals connected wrongly |
Battery deep discharge |
UPS will shut down when battery voltage reaches to 10.4V (Per battery) |
PACKING INFORMATION |
Net weight |
8.4kg |
9 kg |
12.8 kg |
16.5 kg |
Gross weight |
9 kg |
9.8 kg |
12.9 kg |
17.2 kg |
Dimensions |
32.5 x 32.5 x 17.0 cm |
32.5 x 32.5 x 17.0 cm |
38.0 x 35.8 x 18.0 cm |
38.0 x 35.5 x 18.0 cm |