model number |
FA-AVR-150V-10KVA-33CVR |
FA-AVR-150V-20KVA-33CVR |
FA-AVR-150V-45KVA-33CVR |
FA-AVR-150V-80KVA-33CVR |
FA-AVR-150V-150KVA-33CVR |
Capacity |
10KVA/8W |
20KVA/16KW |
45KVA/36KW |
80KVA/64KW |
150KVA/120KW |
INPUT |
Rated INPUT Voltage |
380V (400V, 415V, 440V or 200V, 220V Optional) |
Input Voltage Range |
±15%, ±30%, or customized |
Input Frequency |
50/60Hz ± 5Hz |
Power Factor |
0.98 |
OUTPUT |
Rated Output Voltage |
L1—L2/380V L2—L3/380V L1—L3/380V |
Output Precision |
Preset at ±2% (±2% to ±10% Adjustable) |
Response time |
<1s, against 10% variation of input voltage |
Power Factor |
0.8 |
Efficiency |
>96% |
Loading Ability |
150% for 30s, 200% for 10s, 300% for 1s |
DISPLAY |
INPUT VOLTAGE |
Analog or Digital Voltmeter |
Output VOLTAGE |
Analog or Digital Voltmeter |
OUTPUT CURRENT |
Analog or Digital current meter |
PROTECTION AND ALARM |
Output Over/Under Voltage |
LED + Buzzer Beeping (Output Cutoff Optional) |
Overload |
200kVA~600kVA: Input Cutoff +LED +Buzzer Beeping Short Circuit 800kVA~3,000kVA: LED +Buzzer Beeping |
Over Termperature |
LED + Buzzer Beeping (Output Cutoff Optional) |
Short Circuit |
Input cutoff by air breaker |
WRONG PHASE sequence |
Cant switch on regulator “P” in display + Buszzer beeping |
PHASE FAILURE |
LED + Buzzer Beeping |
Bypass |
Isolated manual bypass switch |
Output Delay time |
6s/180s selectable |
Surge/Spike |
Optional, Replaceable SPD |
SAFETY |
Insulation V / R |
2,000V/60s / >5MΩ |
Creepage Distance |
>8mm |
Grounding Resistance |
>0.1MΩ |
Cooling Mode |
Force Air Cooling |
Audible Noice |
<65dB at 1m distance with full load |
OPERATION CONDITIONS |
operating Termperture |
– 5°C – + 45°C |
Operating humidity |
0%-90%, non-condesing |