3PH CONTACTLESS AVR LAMBDA SERIES 150V (10KVA – 3000KVA)

Benefits

  • The transformer won’t be damaged, if short circuit happened or it’s overloaded in short time. 100% load for long time, 150% for 30 seconds, 200% for 10 seconds, 300% for 5 seconds
  • When output voltage is out of range, or overload, overheat and
    open phase happens, or control circuit is abnormal, it will give buzzer beeping and LED is light (not cut off output).
  • The contactless inductive transformer makes the linear voltage regulation.
  • Manual bypass switch is bundle.
  • No contact point inside the transformer, there is no arc discharge.
  • The winding is made of high purity oxygen-free copper wire, the core is made of high magnetic density silicon-steel plate.
3PH CONTACTLESS AVR LAMBDA SERIES 150V (10KVA - 3000KVA)

Specification

model number FA-AVR-150V-10KVA-33CVR FA-AVR-150V-20KVA-33CVR FA-AVR-150V-45KVA-33CVR FA-AVR-150V-80KVA-33CVR FA-AVR-150V-150KVA-33CVR
Capacity 10KVA/8W 20KVA/16KW 45KVA/36KW 80KVA/64KW 150KVA/120KW
INPUT
Rated INPUT Voltage   380V (400V, 415V, 440V  or 200V, 220V Optional)
Input Voltage Range  ±15%, ±30%, or customized
Input Frequency 50/60Hz ± 5Hz
Power Factor 0.98
OUTPUT
Rated Output Voltage  L1—L2/380V            L2—L3/380V             L1—L3/380V
Output Precision Preset at ±2% (±2% to ±10% Adjustable)
Response time  <1s, against 10% variation of input voltage
Power Factor 0.8
Efficiency >96%
Loading Ability 150% for 30s, 200% for 10s, 300% for 1s
DISPLAY
INPUT VOLTAGE  Analog or Digital Voltmeter
Output VOLTAGE  Analog or Digital Voltmeter
OUTPUT CURRENT  Analog or Digital current meter
PROTECTION AND ALARM
Output Over/Under Voltage LED + Buzzer Beeping (Output Cutoff Optional)
Overload 200kVA~600kVA: Input Cutoff +LED +Buzzer Beeping Short Circuit 800kVA~3,000kVA: LED +Buzzer Beeping
Over Termperature LED + Buzzer Beeping (Output Cutoff Optional)
Short Circuit  Input cutoff by air breaker
WRONG PHASE sequence Cant switch on regulator “P” in display + Buszzer beeping
PHASE FAILURE LED + Buzzer Beeping
Bypass  Isolated manual bypass switch
Output Delay time 6s/180s selectable
Surge/Spike  Optional, Replaceable SPD
SAFETY
Insulation V / R 2,000V/60s /  >5MΩ
Creepage Distance  >8mm
Grounding Resistance  >0.1MΩ
Cooling Mode Force Air Cooling
Audible Noice  <65dB at 1m distance with full load
OPERATION CONDITIONS
operating Termperture  – 5°C – + 45°C
Operating  humidity  0%-90%, non-condesing