Benefits
- Accepts dual-mains inputs
- N+X parallel redundancy (Parallel capability up to 4 units).
- Unique design and fully coating PCBAs to withstand harsh environment
- Emergency power off function (EPO)
- True online double conversion with DSP control
- Front access makes maintenance and replacement easily
- touch colored LCD (Optional )
Specification
MODEL | FA-UPSW-384V- 200KVA-3PH |
FA-UPSW-384V- 250KVA-3PH |
FA-UPSW-384V- 300KVA-3PH |
FA-UPSW-384V- 400KVA-3PH |
Capacity(VA/Watts) | 200KVA /160KW | 250KVA /200KW | 300KVA /240KW | 400KVA /320KW |
INPUT | ||||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (3Ph + N or 3Ph + N + G ) | |||
Acceptable Voltage Range | 304VAC ~ 456VAC | |||
Frequency | 50 Hz ± 5Hz (±10%) | |||
OUTPUT | ||||
Nominal Voltage | 3 x 380VAC/400VAC/415VAC (Selectable ) | |||
Connection Type | Hardwire 5-wire (3 Ph+N+G) | |||
Waveform | Pure Sine wave | |||
Output Voltage Stability |
Steady state | ±1% | ||
Transient state | ±5% | |||
Frequency | 50 Hz | |||
Frequency Synchronization Range | ± 5 Hz (Equal to bypass working range) | |||
Frequency Synchronization Speed | 1~2 Hz/s | |||
Crest Factor | 3:01 | |||
Total Harmonic Distortion (THDv) | <2% (Linear Load), <4% (Non-linear Load) | |||
Dynamic in-rush Voltage Range | 0%->100%->0% (R load) <±5%: 20%->100%->20% (R Load) ± 3% | |||
Dynamic Recovery Time | 0%~100% RCD load: <60 ms recover to 90% of nominal voltage | |||
Phase Displacement | 120º±1% (balanced load) 120º±2% (imbalances 50% of the load) |
|||
Transfer Time | 0 ms | |||
Overload Capability | 0%~110% continuous running; 110%~ 150% for 10 min~1 min; >160% for 200 ms | |||
Short-circuit Capability | 60~100ms | |||
Transient Response Time | < 5ms | |||
BYPASS | ||||
Connection Type | Hardwire 5-wire (3Ph+N+G) | |||
Input Voltage Range | 220VAC ±25% | |||
Overload Capability | 1.5 In~1.8 In 1h~30s | |||
Short-circuit Capability | 1.8 In~ >2.0 In 30s~200ms | |||
BATTERY & CHARGER | ||||
Rectifie | Type | 6 pulse or 12 pulse | ||
Rated output voltage | 384 VDC | |||
Charger voltage | 395VDC~435VDC (Adjustable) | |||
Charging current (max) | 50A 70A | |||
Battery | Type / Numbers | Support VRLA Battery / 32 pcs (29~32 adjustable) | ||
PHYSICAL | ||||
Dimension, DxWxH (mm) | 800 x 1600 x 1800 850 x 1630 x 1900 | 900 x 1700 x 1900 | ||
Net Weight (kgs) | 1700 | 1900 | 2300 | 2500 |
ENVIRONMENT | ||||
Operation Temperature | 0~35ºC continuous running, 40ºC 8-hour running at nominal input voltage, recharging batteries and no overload, 45ºC derating to 85% with linear load |