Model number |
FA-AVR-150V-20KVA/SVR1PH |
Capacity |
20KVA |
Material |
Metal |
INPUT |
Input Voltage |
150-260V or customized |
Input Frequency |
45-65HZ |
Power Factor |
0.98 |
OUTPUT |
Rated Output Voltage |
220V (230V Optional) |
Output Precision |
±3% (±1% optional) |
Response time |
<1s, against 10% variation of input voltage |
Efficiency |
>96% |
Loading Ability |
120% for 180s, 150% for 30s, 200% for 10s, 300% for 5s |
DISPLAY |
Digital Display |
Input voltage, Output voltage, Output current |
PROTECTION AND ALARM |
Output Under Voltage |
Output cuttoff by contactor + “L” in display + Buzzer beeping |
Output Over Voltage |
Output cuttoff by contactor + “H” in display + Buzzer beeping |
Overload |
Output cuttoff by contactor + “F” in display + Buzzer beeping |
Over Termperature |
Output cuttoff by contactor + “C” in display + Buzzer beeping |
Short Circuit |
Input cutoff by air breaker |
Bypass |
Isolated manual bypass switch |
Output Delay time |
6s/180s selectable |
Surge/Spike |
Optional, Replaceable SPD |
SAFETY |
Insulation Voltage |
2,000V/60s |
Insulation Resistance |
>5MΩ |
Creepage Distance |
>8mm |
Grounding Resistance |
>0.1MΩ |
Insulation Class of coil |
Class F (155C) |
Cooling Mode |
Cooling Fan |
IP Level |
IP20 |
Audible Noice |
<65dB at 1m distance with full load |
OPERATING CONDITIONS |
operating Termperture |
– 5°C – + 45°C |
Operating humidity |
10%-90%, non-condesing |
Operating Altitude |
<1,000m |