Model number |
FA-INV-12V-850VA |
Capacity |
850VA |
|
Narrow mode |
Wide mode |
Mains undervoltage cutoff /recovery |
180 V / 190 V |
100 V / 110 V |
Mains overvoltage cutoff /recovery |
265 V / 255 V |
295 V / 285 V |
Battery charging voltage |
180 VAC to 265 VAC |
100 VAC to 295 VAC |
Output voltage (no load) |
230 V |
Changeover time |
≤ 10 miliseconds |
≤ 20 miliseconds |
BATTERY |
|
|
Quick charge current |
15A |
Normal charge current |
12A |
Boost charge voltage |
14.4V |
Float charge voltage |
13.8V |
Low battery cutoff point |
10.4V |
Number of batteries |
1 *12VDC |
Recommended battery |
80 AH to 180 AH |
Charge method |
Constant current, followed by constant voltage |
Output waveform |
Pure sine wave |
Output frequency (UPS mode) |
50 HZ |
Efficiency |
≥80% |
Operation temperature |
0 to 45°C |
LED indicators |
Mains,charging,UPS,low battery, overload |
Audible alarm |
Low battery,overload,short circuit |
PROTECTIONS |
Overload |
105% load on UPS (auto reset within 5 re-tries) |
Overcharge |
Control battery voltage and current through software |
Short circuit |
MCB Tripe in Main mode and UPS gets shut down in Back-up mode |
Thermal |
UPS get shut down when temperature reaches to 95 at inside UPS |
Battery reverse polarity |
DC fuse on PMB will fail when battery terminals connected wrongly |
Battery deep discharge |
UPS will shut down when battery voltage reches to 10.4 (per battery) |
Packing information |
Quantity |
1 piece |
Net weight |
8.4 kg |
Gross weight |
10.3 kg |
Dimensions |
32.5 x 32.5 x 17.0 cm |