Model number |
FA-INV-180V-10KVA |
Capacity |
10000VA |
|
NARROW MODE |
WIDE MODE |
Mains undervoltage cutoff /recovery |
180 V / 190 V |
125 V / 135 V |
Mains overvoltage cutoff /recovery |
260 V / 255 V |
280 V / 275 V |
Output voltage (no load) |
220± 5 V |
Changeover time |
≤ 10 mili sec |
≤ 50 mili sec |
BATTERY |
Quick charge current |
15±2A |
Normal charge current |
15±2A |
Boost charge voltage |
14V/Batt |
Float charge voltage |
13.6V/Batt |
Low battery cutoff point |
10.4V/Batt |
Number of batteries |
15 *12VDC |
Recommended battery |
100 AH to 200 AH |
Charge method |
Constant current ,followed by constant voltage |
Output waveform |
Pure sine wave |
Output frequency (UPS mode) |
50 HZ |
Efficiency |
≥80% |
Operation temperature |
0 to 50°C |
LCD indicators |
Mains,charging,UPS,low battery, overload,Short circuit |
Audible alarm |
Low battery,Overload,short circuit |
PROTECTIONS |
Overload |
105% load on UPS (auto reset within 5 re-tries) |
Overcharge |
Current and voltage charge controller |
Short circuit |
Shut down (UPS mode),MCB trip (AC mode) |
Thermal |
shut down at 93°C |
Battery reverse polarity |
DC fuse on PMB will fail when battery terminals connected wrongly |
Battery deep discharge |
Cutoff at 10.4V battery level |
Packing information |
Quantity |
1 piece |
Net weight |
89 kg |
Dimensions |
55.0 x 35.0 x 65.0 cm |