Benefits
- Wide Input voltage range (110V-300V).
- Adjustable output voltage (220V-240V).
- 50/60 Hz frequency converter mode.
- Input power factor correction.
- True online double-conversion technology with high power density, utility frequency independence.
- Three segment charging mode to increase battery service life, optimize recharge time.
- Selectable High Efficiency mode of operation.
- Cold start function to startup the UPS without utility.
- Parallel capability up to 3 units (for 6KVA & 10KVA).
- Emergency, shutdown control through the remote emergency power-off (EPO) port.
- Power shedding function may turn off uncritical load in battery backup to make longer backup time for critical load.
- Rack-mount design.
Specification
MODEL | FA-UPSX-36V- 1KVA-1PH |
FA-UPSX-36V- 1.5KVA-1PH |
FA-UPSX-48V- 2KVA-1PH |
FA-UPSX-72V- 3KVA-1PH |
FA-UPSX-240V- 6KVA-1PH |
FA-UPSX-240V- 10KVA-1PH |
PHASE | 1 phase in/ 1 phase out | |||||
Capacity(VA/Watts) | 1000 VA/1000 W | 1500 VA/1500 W | 2000 VA/2000 W | 3000 VA/3000 W | 6000 VA/6000 W | 10000 VA/10000 W |
INPUT | ||||||
Input Voltage Range | 160-300 VAC ± 5 % at 100% load 110-300 VAC ± 5% at 50% load | 160-300 VAC ± 5 % at 100% load 110-300 VAC ± 5% at 50% load | 160-300 VAC ± 5 % at 100% load 110-300 VAC ± 5% at 50% load | 160-300 VAC ± 5 % at 100% load 110-300 VAC ± 5% at 50% load | 140-300 VAC @ 60~80 % load; 110-300 VAC @ 0~60% load; 176-300 VAC @ 80~100 % load |
140-300 VAC @ 60~80 % load; 110-300 VAC @ 0~60% load; 176-300 VAC @ 80~100 % load |
Frequency range | 40 Hz ~ 70 Hz | 41 Hz ~ 70 Hz | 42 Hz ~ 70 Hz | 43 Hz ~ 70 Hz | 49 ~54 Hz or 56~64 Hz | 50 ~54 Hz or 56~64 Hz |
Power factor | ≥ 0.99 (100% Load) | |||||
OUTPUT | ||||||
Output voltage | 200/208/220/230/240 VAC | 200/208/220/230/240 VAC | 200/208/220/230/240 VAC | 200/208/220/230/240 VAC | 208/220/230/240 VAC | 208/220/230/240 VAC |
AC Voltage Regulation (Batt. Mode) |
± 1% | |||||
Transfer Time AC to DC | Zero | Zero | Zero | Zero | Zero | Zero |
Transfer Time Inverter to Bypass |
4 ms (Typical) | 5 ms (Typical) | 6 ms (Typical) | 7 ms (Typical) | Zero | Zero |
Waveform (Batt. Mode) | Pure Sine wave | |||||
EFFICIENCY | ||||||
Line Mode | ≥ 91% @ battery fully charged | |||||
ECO Mode | ≥ 96% @ battery fully charged | |||||
Battery Mode | ≥ 90% | ≥ 90% | ≥ 90% | ≥ 90% | 91% | 91% |
BATTERY | ||||||
Stander Battery type | 12V/7 Ah or 12V/ 9 Ah | |||||
External Battery type | Depending on applications (65AH – 200AH) | |||||
Numbers | 3 | 3 | 4 | 6 | 20 | 20 |
Typical Recharge Time | 9 hours recover to 90% capacity | |||||
Charging Current | 200/208/220/230/240 VAC Models: default 2A, max. 12A | default 1A, max. 4A adjustable | default 1A, max. 4A adjustable | |||
Charging Voltage | 41.1 VDC ±1% | 41.1 VDC ±1% | 54.8 VDC ±1% | 82.1 VDC ±1% | 273 VDC ±1% | |
ALARM | ||||||
Battery Mode | Sounding every 5 seconds | |||||
Low Battery | Sounding every 2 seconds | |||||
Overload | Sounding every second | |||||
Fault | Continuously sounding | |||||
ENVIRONMENTAL | ||||||
Humidity | 20-90% RH @ 0- 45°C (Non-condensing) | |||||
Noise Level | Less than 50dBA@1 Meter | |||||
PHYSICAL | ||||||
Dimension D*W*H (mm) | 410 x 438 x 88 | 410 x 438 x 88 | 510 x 438 x 88 | 630 x 438 x 88 | 600x438x88 | |
Net Weight (kgs) | 14.1 | 15.5 | 19.5 | 27.5 | 15 | 18 |